EN
All fan coils
Equipment Dehumidifiers Solutions Blog
ENRU

Product specifications

WSGV-300-VS-4NS

Chilled-water fan coil — Cassette 4-way unit

Download as PDF
The Welkin WSGV-300-VS-4NS — Cassette 4-way unit.
ModelWSGV-300-VS-4NS
SeriesCassette 4-way unit
Air flow (CFM)300
Capacity (ton)0.9
Capacity (kW)3.3
QCC RegistrationRegistered
RegionUAE

Fan coil unit

Power supply (V / Hz / phase)220–240 / 50 / 1
Cooling capacity, H / M / L (W)3300 / 2840 / 2380
Heating capacity, H / M / L (W)4800 / 4200 / 3700
Air flow volume, H / M / L (m³/h)510 / 440 / 360
Air flow volume, H / M / L (CFM)300 / 259 / 212
Water flow (m³/h)0.62
Hydraulic resistance (kPa)26
Max. working pressure (MPa)1.6
Noise level (dB(A))39
Net dimensions (W × D × H, mm)570 × 570 × 260
Packing dimensions (W × D × H, mm)650 × 650 × 290
Net weight (kg)18
Gross weight (kg)20.3
Drain pipeDN20
Inlet / outlet water pipeDN20
Power wiring, indoor (mm²)3 × 1

Fan motor and coil

Fan motor typeLow-noise 3-speed fan motor
Number of fan motors1
Fan motor output (W)55
Capacitor (µF)1.5
Number of fans1
Fan typeCentrifugal, white plastic
Coil rows2
Fin pitch (mm)1.5
Fin materialHydrophilic aluminium fin
Tube outside Ø (mm) and typeØ 7, inner grooved

Panel

Net dimensions (W × D × H, mm)650 × 650 × 55
Packing dimensions (W × D × H, mm)710 × 710 × 80
Net weight (kg)3
Gross weight (kg)5

Product features

Return air plenum and filter

Comes with the return plenum and an air filter as standard — nothing extra to source for the install.

Adjustable ESP

The fan’s external static pressure can be set to suit the duct run.

External static pressure

Rated with pressure in hand for ducting, grilles and filters — not a bare free-blow figure.