EN
All VRF models
Equipment Dehumidifiers Solutions Blog
ENRU

Product specifications

WSTBFJF-J220-MT1FV

VRF system — High ESP duct indoor unit

Download as PDF
The Welkin WSTBFJF-J220-MT1FV — VRF High ESP duct indoor unit.
ModelWSTBFJF-J220-MT1FV
SeriesHigh ESP duct indoor unit
Capacity (ton)6.3
Capacity (kW)23
QCC RegistrationRegistered
RegionUAE

Indoor unit

Power supply (V / Hz / phase)220–240 / 50 (60) / 1
Cooling capacity (kW)22.4
Heating capacity (kW)25
Indoor air flow by fan speed, high → low (m³/h)4400
Noise level by fan speed, high → low (dB(A))57
External static pressure, default (range) (Pa)170 (30–250)
Net dimensions (W × D × H, mm)1388 × 715 × 480
Packing dimensions (W × D × H, mm)1540 × 810 × 610
Net weight (kg)99
Gross weight (kg)120
Operating temperature (°C)16–32
Application area (m²)100–200

Fan motor and coil

Fan motor modelFP900B-ZL
Fan motor brandWOLONG
Fan motor output (W)1200
Fan speed by setting, high → low (rpm)1350
Coil rows4
Fin pitch (mm)1.6
Fin materialHydrophilic aluminium fin
Tube outside Ø (mm) and typeØ 7, inner grooved
Heat exchange area (m²)26.9

Refrigerant pipe and wiring

Refrigerant pipe, liquid side, Ø (mm)12.7
Refrigerant pipe, gas side, Ø (mm)22.2
DrainageR3/4 in (DN20)
Power wiring, indoor (mm²)3 × 1.5
A/B signal wiring, IDU–ODU and IDU–IDU (mm²)2 × 0.5

Product features

Flexible air intake

Intake options to suit the ceiling void on the 36K size.

Two return air modes

Return air from the back or from underneath — the duct layout decides, not the unit.

Two-way drain connection

The condensate drain can leave the unit on either side, whichever suits the pipework.